Altitude: ≤ 2000 m.
Temperature range: -5 °C to +40 °C, and the average temperature within 24 hours should not exceed +35 °C.
The relative humidity should not exceed 50% at +40 °C, and higher relative humidity is allowed at low temperature (90% at +20 °C). And air must be clean.
Workplaces should be free of fire, explosion, serious pollution, chemical corrosion and severe vibration.
Gradient: ≤ 5°, vertical installation.
Temperature range of transportation & storage: -25 °C to +55°C, and the temperature can be up to +70 °C in short time (within 24 hours).
Technical parameters |
||
Items |
Parameters |
|
Rated insulation voltage (V) |
660 |
|
Rated operating voltage (V) |
380/660 |
|
Auxiliary circuit rated voltage (V) |
AC |
220/380 |
DC |
110/220 |
|
Operating frequency (Hz) |
50 - 60 |
|
Rated current (A) |
Horizontal bus-bar |
< 3150 |
Vertical bus-bar |
630/800 |
|
Rated short-time withstand current |
Midline (kA/1 s) |
50 |
Bus-bar (kA/1 s) |
30 |
|
Rated peak current (kA/0.1 s) |
105/50 |
|
Functional unit breaking capacity (kA) |
50 (effective value) |
|
Cabinet protection degree |
IP40 |
|
Bus-bar |
Three phase four wire system, three phase five wire system |
|
Operating mode |
On-site, distance and automatic |
We provide technical support and complete power distribution solutions tailored to your needs. If the design drawings you provide are deemed unfeasible, we will optimize the plan and adjust it with the dimensions of the cabinet, the location of the equipment, and so on. We will also optimize the configuration of the products to make them meet your requirements.
If any problem occurs, we will first provide support by phone or email. We will perform a remote debug if necessary. Furthermore, our products come with a troubleshooting manual for reference when trying to find the fault and solve issues by yourself. Most problems can be solved by the above-mentioned methods. We will check in every year or so to acquire detailed information about your equipment to get a better understanding of the inner workings.
1. We will quickly solve the problem after receiving the issue report or repair request.
2. We then explain the cause of failure in detail and any fees will be charged according to market pricing.
3. If we take any parts back for inspecting, we will apply fragile notice stickers on them or write their serial number down to maintain the safety of the parts.
4. If your complaint is deemed valid, we will refund repair fees to you on-site.